Place of use
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
Product Code | Dimension and Weights | Electrical Properties | |||||||||
Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
In Ground at 20° C | On Air at 30° C | ||||||||||
28-29000001 | 4x10 | 22.0 | 1150 | 1000 | 1.83 | 75 | 60 | ||||
28-29000002 | 4x16 | 24.5 | 1500 | 1000 | 1.15 | 98 | 80 | ||||
28-29000003 | 4x25 | 28.0 | 2050 | 1000 | 0.727 | 128 | 106 | ||||
28-29000004 | 4x35 | 31.0 | 2600 | 1000 | 0.524 | 157 | 131 | ||||
28-29000005 | 4x50 | 35.0 | 3450 | 1000 | 0.387 | 185 | 159 | ||||
28-29000006 | 4x70 | 39.5 | 4500 | 1000 | 0.268 | 228 | 202 | ||||
28-29000007 | 4x95 | 45.0 | 5850 | 500 | 0.193 | 275 | 244 | ||||
28-29000008 | 4x120 | 49.0 | 7150 | 500 | 0.153 | 313 | 282 | ||||
28-29000009 | 4x150 | 54.0 | 8700 | 500 | 0.124 | 353 | 324 | ||||
28-29000010 | 4x185 | 59.5 | 10650 | 500 | 0.0991 | 399 | 371 | ||||
28-29000011 | 4x240 | 67.0 | 13550 | 250 | 0.0754 | 464 | 436 |